26 Pressure transmitter D81 METEC
®
250
Ri < 250
+
-
PLC
Setup
4.4 Setup with HART
®
handheld
Sensors with electronics versions I, K and L
can be set up with the HART
®
handheld. A
special DD (Data Device Description) is not
necessary. Just connect the HART
®
handheld
to the sensor signal cable after you have
connected the sensor to supply voltage.
Note:
If the resistance of the voltage supply is less
than 250 , a resistor must be looped into the
signal/connection cable during adjustment.
The digital adjustment and communication
signals would otherwise be short-circuited
through insufficient resistance of e.g. the
supply voltage source or the processing
system. Simply connect the adjustment resis-
tor in parallel to the connection socket of the
HART
®
handheld.