6 Set up with the display and adjustment module
MINITRAC 31 • 4 … 20 mA/HART - four-wire
40447-EN-131119
For this purpose, check which isotope is integrated in the source
container.Youcanndthisinformationonthetypelabelofthesource
container.
Enter here, the respective application.
This menu item enables adaptation of the sensor to the requested ap-
plication. You can choose between the following applications: "Level",
"Density", "Limit level", "X-ray alarm" or "Real value correction".
Thenaturalradiationonearthinuencestheaccuracyofthemeas-
urement.
With this menu item the natural background radiation can be faded
out.
For this purpose, the MINITRAC 31 measures the natural background
radiationandsetsthepulseratetozero.
In the future, the pulse rate from this background radiation will be
automatically deducted from the total pulse rate. This means: only
the component of the pulse rate originating from the source will be
displayed.
The source container must be closed for this setting.
In this menu item you can select the units of the process value and
the temperature.
In this menu item you can enter the measuring range (min. and max.
process value) of the sensor.
Thesesettingsinuencethecurrentoutputofthesensor.
Enter in the menu window "Max. process value" the max. level (full),
for example in "m". This corresponds to an output current of 20 mA.
Enter in the menu window "Min. process value" the min. level (empty),
for example in "m". This corresponds to an output current of 4 mA.
In this menu item you can carry out the adjustment of the sensor.
Due to the measuring principle, there is no linear relationship between
pulse rate and level. Hence, this adjustment (i.e. linearisation) must in
any case be carried out.
Note:
Ifyoucannotllthevesselwiththeoriginalmedium,itisalsopossible
to carry out the adjustment with water.
Prerequisites:
Radiation is switched on - Source container is set to "ON"
Thevesseliseithercompletelylled(100%)orcompletelyemptied
(0 %).
Dependingonthefactifthevesselislledoremptied,youcancar-
riedoutrstthefullortheemptyadjustment.TheMINITRAC31sorts
the points automatically according to their level.
Select "Show table"todisplayandeditthelinearizationpoints.
Select "Linearization - New"toentertherstpoint.
Setup - Application
Setup - Background
radiation
Setup - Units
Setup - Adjustment
Setup - Linearization