9 Diagnostics and service
MINITRAC 31 • 4 … 20 mA/HART - four-wire
40447-EN-131119
Code
Text mes-
sage
Cause Rectication
F120
Filter time
error
Faulty or missing instrument
adjustment
Carrying out adjustment
F121
Faulty partici-
pant list on the
multisensor
communica-
tion bus
Slave instruments not found Check Slave instruments
Check Slave list in Master
instrument
Slave instrument with wrong
address
F122
Double ad-
dresses on
the mul-
tisensor
communica-
tion bus
Instrument addresse was
assigned several times
Change instrument
addresses
F123
X-ray alarm
External instruments cause
radiation
Determine reason for X-ray
alarm
In case of brief X-ray radia-
tion: Monitor switching out-
puts for this time manually
F124
Alarm due to
increased ra-
diation
Radiation dose too high Determine reason for
increased radiation
F125
Ambient tem-
perature too
high
Ambient temperature on
the housing outside the
specication
Cool the instrument or pro-
tect it with isolating material
against radiation heat
The following table shows the error codes and text messages in the
status message "Function check" and provides information on causes
as well as corrective measures.
Code
Text mes-
sage
Cause Rectication
C029
Simulation
Simulation active Finish simulation
Wait for the automatic end
after 60 mins.
The following table shows the error codes and text messages in the
status message "Outofspecication" and provides information on
causes as well as corrective measures.
Function check
Outofspecication