23
6 Set up with the display and adjustment module PLICSCOM
VEGABAR 52 • 4 … 20 mA
36716-EN-130321
– Save value
•
[->] key to select:
– Menu change
– Select list entry
– Select editing position
•
[+] key:
– Change value of the parameter
•
[ESC] key:
– interrupt input
– Jump to next higher menu
The sensor is adjusted via the four keys of the display and adjust-
ment module. The LC display indicates the individual menu items. The
functions of the individual keys are shown in the above illustration.
Approx. 10 minutes after the last pressing of a key, an automatic reset
tomeasuredvalueindicationistriggered.Anyvaluesnotconrmed
with [OK] will not be saved.
6.4 Setup steps
VEGABAR 52 can be used for level as well as for process pressure
measurement. Default setting is level measurement. The mode can be
changed in the adjustment menu.
Dependingontheapplicationonlytherespectivesubchapter"Level
orprocesspressuremeasurement"isofimportance.There,yound
the individual adjustment steps.
Level measurement
Set up VEGABAR 52 in the following sequence:
1. Selecting adjustment unit/density unit
2. Carry out a position correction
3. Carry out min. adjustment
4. Carry out max. adjustment
Inthemenuitem"Adjustment unit"youselectthephysicalunitin
which the adjustment should be carried out, e.g. mbar, bar, psi…
Thepositioncorrectioncompensatestheinuenceofthemounting
positionorstaticpressureonthemeasurement.Itdoesnotinuence
the adjustment values.
Information:
The steps 1, 3 and 4 are not necessary for instruments which are
alreadypresetaccordingtocustomerspecications!
Youcanndthedataonthetypelabelontheinstrumentorinthe
menu items of the min./max. adjustment.
The display and adjustment module enables the adjustment without
llingorpressure.Thankstothis,youcancarryoutyoursettings
already in the workshop without the instrument having to be installed.
Adjustment system
Le
vel or process pres-
sure measurement
Parameter adjustment
"Level measurement"