8Maintenanceandfaultrectication
VEGABAR 52 • 4 … 20 mA
36716-EN-130321
Total deviation analogue output signal absolute:
F
total
= 0.365 % x 8 bar/100 % = 29.2 mbar
8.4 Exchanging the electronics module
In case of a defect, the electronics module can be exchanged by the
user against an identical type. If no electronics module is available on
side, the module can be ordered from the agency serving you.
Ordering and exchange are possible with or without sensor serial
number. The electronics module with serial number includes order-
specic data such as factory setting, seal material etc. These are not
included in the electronics module without serial number.
The serial number is stated on the type label of VEGABAR 52 or on
the delivery note.
8.5 Software update
The software version of VEGABAR 52 can be determined as follows:
on the type label of the electronics
Via the display and adjustment module
via PACTware
You can view all software histories on our website www.vega.com.
Make use of this advantage and get registered for update information
via e-mail.
The following components are required to update the sensor soft-
ware:
Sensor
Voltage supply
VEGACONNECT
PC with PACTware
Currentsensorsoftwareasle
At"www.vega.com/downloads"goto"Software".Selectunder"plics
sensors and instruments","Firmware updates"therespectiveinstru-
mentseriesandsoftwareversion.Loadthezipleviatherightmouse
keywith"Save target as"e.g.onthedesktopofyourPC.Movewith
therightmousekeytothefolderandselect"Extract all".Savethe
extractedles,forexampleonthedesktop.
Connect the signal conditioning instrument to power supply and
provide the connection from the PC to the instrument via the interface
adapter.StartPACTwareandgoviathemenu"Project"totheVEGA
project assistant.Select"USB"and"Set instruments online".Activate
theprojectassistantwith"Start".Theassistantestablishesthecon-
nection automatically and opens the parameter adjustment window
"Sensor # online parameter adjustment".Connectthisparameter
adjustment window before you carry out further steps.
Select with the right mouse key the sensor in the project and go to
"Additional function
".Thenclickto"Software update".Thewindow
"Sensor # software update"opens.PACTwarechecksnowthesensor
Load sensor software
to PC
Prepare update
Load software into sen-
sor