Vega VEGABAR 52 Foundation Fieldbus - climate compensat Bedienungsanleitung Seite 60

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 76
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 59
60
10 Annexe
VEGABAR 52 • Foundation Fieldbus - à compensation climatique
36789-FR-130410
Write access resets to current value
min_peak_sensor_value
Holds the minimum sensor value. Write access resets to current value. Unit derives from 'Sen-
sor_range.unit'
Write access resets to current value
CAL_POINT_HI
Highest calibrated value. For calibration of the high limit point you give the high measurement
value (pressure) to the sensor and transfer this point as HIGH to the transmitter. Unit derives
from 'Sensor_range.unit'
CAL_POINT_LO
Lowest calibrated value. For calibration of the low limit point you give the low measurement
value (pressure) to the sensor and transfer this point as LOW to the transmitter. Unit derives
from 'Sensor_range.unit'
CAL_MIN_SPAN
Minimum calibration span value allowed. Necessary to ensure that when calibration is done,
the two calibrated points (high and low) are not too close together. Unit derives from 'Sen-
sor_range.unit'
SCALE_IN
Min/max-adjustment: Upper and lower calibrated points of the sensor. Unit derives from 'Sen-
sor_range.unit'
trimmed_value
Sensor value after the trim processing. Unit derives from 'Sensor_range.unit'
sensor_sn
Sensor serial number
temperature
Process temperature. Selected as input to AIFB by setting 'Channel' = 4. Unit derives from
'Temperature.unit'
temperature_unit
Unit code of 'Temperature', 'Max/Min_peak_temperature_value'
°C, °F, K, °R
max_peak_temperature_value
Holds the maximum process temperature. Write access resets to current value. Unit derives
from 'Temperature.unit'
Write access resets to current value
min_peak_temperature_value
Holds the minimum process temperature. Write access resets to current value. Unit derives
from 'Temperature.unit'
Write access resets to current value
10.3 Encombrement
Les dessins cotés suivants ne représentent qu'une partie des versions possibles. Vous pouvez
télécharger des dessins cotés détaillés surwww.vega.com sous "Téléchargements" et "Dessins".
Les boîtiers à deux chambres ne sont disponibles qu'en version Ex-d pour les appareils avec sortie
signal 4 … 20 mA.