5 Connecting to power supply
VEGABAR 67 • 4 ... 20 mA/HART
36742-EN-130321
housing.Thiswouldinuencethestabilityoftheconnectionandthe
tightness of the housing.
If screened cable is necessary, connect the cable screen on both
ends to ground potential. In the sensor, the screen must be connected
directly to the internal ground terminal. The ground terminal on the
outside of the housing must be connected to the potential equalisa-
tion (low impedance).
If potential equalisation currents are expected, the connection on the
processing side must be made via a ceramic capacitor (e. g. 1 nF,
1500 V). The low-frequency potential equalisation currents are thus
suppressed,buttheprotectiveeectagainsthighfrequencyinterfer-
ence signals remains.
Warning:
Considerablepotentialdierencesexistinsidegalvanicplantsaswell
as vessels with cathodic corrosion protection. Very large equalisa-
tioncurrentscanowthroughthecablescreenwhenthescreen
is grounded on both ends. To avoid this, the cable screen must be
connected to ground potential only on one end (inside the switch-
ing cabinet) in such applications. The cable screen must not be
connected to the internal ground terminal in the sensor and the outer
ground terminal on the housing not to potential equalisation!
Information:
Themetallicpartsoftheinstrument(transmitter,processtting,etc.)
are conductively connected with the inner and outer ground terminal
on the housing. This connection exists either as a direct metallic
contact or via the shielding of the special connection cable on instru-
mentswithexternalelectronics.Youcanndspecicationsonthepo-
tentialconnectionswithintheinstrumentinchapter"Technical data".
Take note of the corresponding installation regulations for Ex applica-
tions. In particular, make sure that no potential equalisation currents
owoverthecablescreen.Incaseofgroundingonbothsidesthis
can be achieved by the use of a capacitor or a separate potential
equalisation.
5.2 Connection procedure
Proceed as follows:
1. Unscrewthehousingcover
2. If a display and adjustment module is installed, remove it by turn-
ing it to the left.
3. Loosen compression nut of the cable entry
4. Remove approx. 10 cm of the cable mantle, strip approx. 1 cm
insulation from the individual wires
5. Insert the cable into the sensor through the cable entry
6. Lift the opening levers of the terminals with a screwdriver (see
following illustration)
7. Insert the wire ends into the open terminals according to the wir-
ing plan
Cable screening and
grounding
Single/Double chamber
housing