31
6 Set up with the display and adjustment module
VEGABAR 81 • Modbus and Levelmaster protocol
46293-EN-131107
Temperature unit:
Enter the requested parameters via the appropriate keys, save your
settings with [OK] and jump to the next menu item with the [ESC] and
the [->] key.
Especially with chemical seal systems, the installation position of the
instrumentcanshift(oset)themeasuredvalue.Positioncorrection
compensatesthisoset.Intheprocess,theactualmeasuredvalue
is taken over automatically. With relative pressure measuring cells a
manualosetcanalsobecarriedout.
If the actual measured value should be taken over as correction value
duringautomaticpositioncorrection,thisvaluemustnotbeinu-
enced by product coverage or static pressure.
Withthemanualpositioncorrection,theosetvaluecanbedeter-
mined by the user. Select for this purpose the function "Edit" and
enter the requested value.
Save your settings with [OK] and move with [ESC] and [->] to the
next menu item.
After the position correction is carried out, the actual measured value
is corrected to 0. The corrective value appears with an inverse sign as
osetvalueinthedisplay.
The position correction can be repeated as often as necessary. How-
ever, if the sum of the corrective values exceeds 20 % of the nominal
measuring range, then no position correction is possible.
VEGABAR 81 always measures pressure independently of the pro-
cess variable selected in the menu item "Application". To output the
selected process variable correctly, an allocation to 0 % and 100 % of
the output signal must be carried out (adjustment).
With the application "Level", the hydrostatic pressure, e.g. with full
and empty vessel, is entered for adjustment. See following example:
Setup - Position correc-
tion
Setup - Adjustment