Vega VEGAPULS 61 (≥ 2.0.0 - ≥ 4.0.0) Profibus PA Bedienungsanleitung Seite 1

Stöbern Sie online oder laden Sie Bedienungsanleitung nach Ausrüstung Vega VEGAPULS 61 (≥ 2.0.0 - ≥ 4.0.0) Profibus PA herunter. VEGA VEGAPULS 61 (≥ 2.0.0 - ≥ 4.0.0) Profibus PA User Manual Benutzerhandbuch

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken

Inhaltsverzeichnis

Seite 1 - VEGAPULS 61

Operating InstructionsRadar sensor for continuous level measurement of liquidsVEGAPULS 61 Probus PADocument ID: 36501

Seite 2 - Quick start

103 Product descriptionVEGAPULS 61 • Probus PA36501-EN-1210113 Product description3.1 CongurationThe type label contains the most important data

Seite 3

113 Product descriptionVEGAPULS 61 • Probus PA36501-EN-121011The instrument is available in two dierent electronics versions. Each version can be i

Seite 4 - Contents

123 Product descriptionVEGAPULS 61 • Probus PA36501-EN-121011The packaging of standard instruments consists of environment-friendly, recyclable card

Seite 5

133 Product descriptionVEGAPULS 61 • Probus PA36501-EN-121011The PLICSMOBILE T61 is an external GSM/GPRS radio unit for transmission of measured val

Seite 6 - 1 About this document

144 MountingVEGAPULS 61 • Probus PA36501-EN-1210114 Mounting4.1 General instructionsWith instruments with threaded process tting, suitable tools m

Seite 7 - 2 For your safety

154 MountingVEGAPULS 61 • Probus PA36501-EN-121011Fig. 5: Flange mounting of the radar sensor4.3 Mounting preparations, mounting strapThe mounting

Seite 8

164 MountingVEGAPULS 61 • Probus PA36501-EN-121011Fig. 6: Adjustment of the angle of inclinationFig. 7: Turning by fastening in the centre4.4 Instr

Seite 9

174 MountingVEGAPULS 61 • Probus PA36501-EN-121011dished or round vessel tops, multiple echoes can arise. These can, however, be suppressed by an ap

Seite 10 - 3 Product description

184 MountingVEGAPULS 61 • Probus PA36501-EN-121011Fig.11:MountingoftheradarsensorwithinowingmediumA corresponding collar ange for DN 80 (

Seite 11

194 MountingVEGAPULS 61 • Probus PA36501-EN-121011dhThe below charts specify the max. socket piece length h depending on the diameter d.Socket diame

Seite 12

2Quick startVEGAPULS 61 • Probus PA36501-EN-121011Quick startThe quick start enables a quick setup with many applications. You can nd further infor

Seite 13

204 MountingVEGAPULS 61 • Probus PA36501-EN-121011The socket piece should be dimensioned in such a way that the an-tenna end protrudes at least 10 m

Seite 14 - 4 Mounting

214 MountingVEGAPULS 61 • Probus PA36501-EN-121011Make sure when planning your measuring site that the radar sensor has a "clear view" to

Seite 15

224 MountingVEGAPULS 61 • Probus PA36501-EN-121011When using a surge pipe in a vessel, inuences from vessel installa-tions and turbulences can be e

Seite 16

234 MountingVEGAPULS 61 • Probus PA36501-EN-121011• The tube diameter must be at least DN 40 or 1½" with antenna size 40 mm (1½")• For the

Seite 17 - > 200 mm

244 MountingVEGAPULS 61 • Probus PA36501-EN-1210110 %100 %125436Fig.21:Congurationbypass1 Radar sensor2 Marking of the polarisation direction3

Seite 18

254 MountingVEGAPULS 61 • Probus PA36501-EN-121011• The measurement through a ball valve with complete run is pos-sibleConstructional requirements o

Seite 19

264 MountingVEGAPULS 61 • Probus PA36501-EN-12101123 ... 4 x hmax90°hmaxd1BFig.23:FlowmeasurementwithKhafagi-Venturiume:d=Min.distanceto

Seite 20 - Fig. 17: Alignment in liquids

275 Connecting to the bus systemVEGAPULS 61 • Probus PA36501-EN-1210115 Connecting to the bus system5.1 Preparing the connectionAlways keep in min

Seite 21 - Fig. 19: Agitators

285 Connecting to the bus systemVEGAPULS 61 • Probus PA36501-EN-121011ceramic capacitor (e.g. 1 nF, 1500 V). Low-frequency potential equali-sation c

Seite 22

295 Connecting to the bus systemVEGAPULS 61 • Probus PA36501-EN-121011You can nd further information to the max. wire cross-section under "Tec

Seite 23

3Quick startVEGAPULS 61 • Probus PA36501-EN-1210113. Select in the menu item "Application" the vessel, the application and the vessel for

Seite 24

305 Connecting to the bus systemVEGAPULS 61 • Probus PA36501-EN-121011115005162738490516273849101678Bus2312+( )(-)Fig. 26: Electronics compartment,

Seite 25 - ≥ 2 mm x h

315 Connecting to the bus systemVEGAPULS 61 • Probus PA36501-EN-1210115.5 Wiring plan, double chamber housing Ex d415005162738490516273849101678Bus

Seite 26 - 2 Venturiume

325 Connecting to the bus systemVEGAPULS 61 • Probus PA36501-EN-121011Contact pin Colour connection ca-ble in the sensorTerminal, electronics module

Seite 27 - 5.1 Preparing the connection

335 Connecting to the bus systemVEGAPULS 61 • Probus PA36501-EN-1210115005162738490516273849101678Bus21312+( )(-)Fig. 33: Address selection switch1

Seite 28 - 5.2 Connecting

346 Set up with the indicating and adjustment moduleVEGAPULS 61 • Probus PA36501-EN-1210116 Set up with the indicating and adjustment module6.1 In

Seite 29

356 Set up with the indicating and adjustment moduleVEGAPULS 61 • Probus PA36501-EN-1210111 2Fig. 35: Insertion of the indicating and adjustment mod

Seite 30 - SIM-Card

366 Set up with the indicating and adjustment moduleVEGAPULS 61 • Probus PA36501-EN-121011 – Edit parameter – Save value• [->] key: – Presentatio

Seite 31

376 Set up with the indicating and adjustment moduleVEGAPULS 61 • Probus PA36501-EN-121011tion. With bulk solids, these are dust generation, materia

Seite 32

386 Set up with the indicating and adjustment moduleVEGAPULS 61 • Probus PA36501-EN-121011• Process/measurement conditions: – Condensation – Smooth

Seite 33

396 Set up with the indicating and adjustment moduleVEGAPULS 61 • Probus PA36501-EN-121011 – Joins like anges, weld joints – Shifting of the runnin

Seite 34

4ContentsVEGAPULS 61 • Probus PA36501-EN-121011Contents1 About this document1.1 Function ...

Seite 35 - 6.2 Adjustment system

406 Set up with the indicating and adjustment moduleVEGAPULS 61 • Probus PA36501-EN-121011 – Exact measurement result required – Distance to the wat

Seite 36 - 6.3 Parameter adjustment

416 Set up with the indicating and adjustment moduleVEGAPULS 61 • Probus PA36501-EN-121011• Vessel of concrete or metal, also multiple chamber silo:

Seite 37

426 Set up with the indicating and adjustment moduleVEGAPULS 61 • Probus PA36501-EN-121011Also the vessel form can inuence the measurement apart fr

Seite 38

436 Set up with the indicating and adjustment moduleVEGAPULS 61 • Probus PA36501-EN-121011ing the product level. These settings can be made ahead of

Seite 39

446 Set up with the indicating and adjustment moduleVEGAPULS 61 • Probus PA36501-EN-1210114. Enter the appropriate distance value in m (correspondi

Seite 40

456 Set up with the indicating and adjustment moduleVEGAPULS 61 • Probus PA36501-EN-121011curve is continuously updated. With the [OK] key, a submen

Seite 41

466 Set up with the indicating and adjustment moduleVEGAPULS 61 • Probus PA36501-EN-121011Note:Check the distance to the product surface, because if

Seite 42

476 Set up with the indicating and adjustment moduleVEGAPULS 61 • Probus PA36501-EN-121011by the user, particularly when setting the switching point

Seite 43

486 Set up with the indicating and adjustment moduleVEGAPULS 61 • Probus PA36501-EN-121011Menu Menu item Default valueSetup Measurement loop nameSen

Seite 44

496 Set up with the indicating and adjustment moduleVEGAPULS 61 • Probus PA36501-EN-121011The following data or settings for adjustment of the indic

Seite 45

5ContentsVEGAPULS 61 • Probus PA36501-EN-1210119.1 Maintenance ... 539.2 Measured

Seite 46

507 Setup with PACTwareVEGAPULS 61 • Probus PA36501-EN-1210117 Setup with PACTware7.1 Connect the PC312Fig. 38: Connection of the PC directly to t

Seite 47

517 Setup with PACTwareVEGAPULS 61 • Probus PA36501-EN-121011Fig. 39: Example of a DTM viewAll device DTMs are available as a free-of-charge standar

Seite 48

528 Set up with other systemsVEGAPULS 61 • Probus PA36501-EN-1210118 Set up with other systems8.1 DD adjustment programsDevice descriptions as Enh

Seite 49

539 Diagnosis, Asset Management and serviceVEGAPULS 61 • Probus PA36501-EN-1210119 Diagnosis, Asset Management and service9.1 MaintenanceIf the dev

Seite 50 - 7 Setup with PACTware

549 Diagnosis, Asset Management and serviceVEGAPULS 61 • Probus PA36501-EN-121011Further echo curves: Up to 10 echo curves can be stored in a ring b

Seite 51

559 Diagnosis, Asset Management and serviceVEGAPULS 61 • Probus PA36501-EN-121011The following table shows the codes and text messages of the status

Seite 52 - 8 Set up with other systems

569 Diagnosis, Asset Management and serviceVEGAPULS 61 • Probus PA36501-EN-121011CodeText mes-sageCause Rectication PA DevS-pecDiagnosisF260Error i

Seite 53

579 Diagnosis, Asset Management and serviceVEGAPULS 61 • Probus PA36501-EN-121011The following table shows the error codes and text messages in the

Seite 54 - 4 Maintenance - blue

589 Diagnosis, Asset Management and serviceVEGAPULS 61 • Probus PA36501-EN-121011The below tables show typical examples of application-related meas-

Seite 55

599 Diagnosis, Asset Management and serviceVEGAPULS 61 • Probus PA36501-EN-1210119.4 MeasurementerrorduringllingFault description Error pattern

Seite 56

61 About this documentVEGAPULS 61 • Probus PA36501-EN-1210111 About this document1.1 FunctionThis operating instructions manual provides all the in

Seite 57 - 9.4 Rectify faults

609 Diagnosis, Asset Management and serviceVEGAPULS 61 • Probus PA36501-EN-1210119.4 Measurement error during emptyingFault description Error patte

Seite 58

619 Diagnosis, Asset Management and serviceVEGAPULS 61 • Probus PA36501-EN-121011In both cases, the serial number of the sensor is needed. The seria

Seite 59

6210 DismountingVEGAPULS 61 • Probus PA36501-EN-12101110 Dismounting10.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous process

Seite 60

6311 SupplementVEGAPULS 61 • Probus PA36501-EN-12101111 Supplement11.1 Technical dataGeneral data316L corresponds to 1.4404 or 1.4435Materials, wet

Seite 61

6411 SupplementVEGAPULS 61 • Probus PA36501-EN-121011Max. torque for NPT cable glands and Conduit tubes Ʋ Plastic housing 10 Nm (7.376 lbf ft) Ʋ Alu

Seite 62 - 10 Dismounting

6511 SupplementVEGAPULS 61 • Probus PA36501-EN-121011Number of FBs with AI (function blocks with analogue input)3Default values Ʋ 1. FB PV Ʋ 2. FB S

Seite 63 - 11 Supplement

6611 SupplementVEGAPULS 61 • Probus PA36501-EN-1210110,5 m (1.6 ft)10 mm (0.394 in)- 10 mm (- 0.394 in)2 mm (0.079 in)- 2 mm (- 0.079 in)0123Fig. 57

Seite 64 - 4 Useful measuring range

6711 SupplementVEGAPULS 61 • Probus PA36501-EN-121011 Ʋ Max. power density in a distance of 1 m< 1 µW/cm²Ambient conditionsAmbient, storage and t

Seite 65 - 2 Antenna edge

6811 SupplementVEGAPULS 61 • Probus PA36501-EN-121011 Ʋ Wire cross-section 0.5 mm² (AWG 20) Ʋ Wire resistance < 0.036 Ω/m Ʋ Tensile strength <

Seite 66

6911 SupplementVEGAPULS 61 • Probus PA36501-EN-121011 Ʋ Ex 10Electrical protective measuresProtection, depending on housing version Ʋ Plastic housin

Seite 67

72 For your safetyVEGAPULS 61 • Probus PA36501-EN-1210112 For your safety2.1 Authorised personnelAll operations described in this operating instru

Seite 68

7011 SupplementVEGAPULS 61 • Probus PA36501-EN-121011Device name Instrument ID GSDlenameVEGA Instrument class in prole3.02VEGA Prole-specicVE

Seite 69 - 11.3 ID number

7111 SupplementVEGAPULS 61 • Probus PA36501-EN-121011 – Out value of the AI FB3 after scaling• Free Place – This module must be used if a value in t

Seite 70 - 11.4 Cyclicaldatatrac

7211 SupplementVEGAPULS 61 • Probus PA36501-EN-121011Byte nByte n+1Bit7VZExponentBit62Bit52Bit42Bit32Bit22Bit12Bit02Bit72Bit62Bit52Bit42Bit32Bit22Bi

Seite 71

7311 SupplementVEGAPULS 61 • Probus PA36501-EN-121011Status code Description according to ProbusstandardPossible cause0 x 89 good (non-cascade) -

Seite 72

7411 SupplementVEGAPULS 61 • Probus PA36501-EN-121011Aluminium housing21ø 86 mm (3.39")~ 116 mm (4.57")116 mm (4.57")M20x1,5M20x1,5/½

Seite 73 - Plastic housing

7511 SupplementVEGAPULS 61 • Probus PA36501-EN-121011Stainless steel housing~ 69 mm(2.72")ø 79 mm(3.11")117 mm (4.61")M20x1,5/½ NPT~

Seite 74 - Aluminium housing

7611 SupplementVEGAPULS 61 • Probus PA36501-EN-121011VEGAPULS 61, threaded versionSW 50 mm(1.97")43 mm(1.69")20 mm(0.79")78 mm (3.07&

Seite 75 - Stainless steel housing

7711 SupplementVEGAPULS 61 • Probus PA36501-EN-121011VEGAPULS61,hygienictting1 2 3 123SW 50 mm(1.97")SW 50 mm(1.97")SW 50 mm(1.97&quo

Seite 76 - VEGAPULS 61, threaded version

7811 SupplementVEGAPULS 61 • Probus PA36501-EN-121011VEGAPULS 61, version with mounting strap125 mm(4.92")2,5 mm(0.10")75 mm(2.95")10

Seite 77 - VEGAPULS61,hygienictting

7911 SupplementVEGAPULS 61 • Probus PA36501-EN-121011VEGAPULS61,versionwithmountingstrapandreector115,5 mm (4.55")218 mm (8.58")45

Seite 78 - 36501-EN-121011

82 For your safetyVEGAPULS 61 • Probus PA36501-EN-1210112.5 CE conformityThe device fullls the legal requirements of the applicable EC guide-lines

Seite 79 - (0.35")

8011 SupplementVEGAPULS 61 • Probus PA36501-EN-121011VEGAPULS61,versionwithcompressionange126 mm(4.96")10,5 mm(0.41")19 mm(0.75"

Seite 80

8111 SupplementVEGAPULS 61 • Probus PA36501-EN-121011VEGAPULS61,versionwithadapterange21138 mm (5.43")31 mm(1.22")20 mm(0.79")8

Seite 81 - 1 Adapterange

8211 SupplementVEGAPULS 61 • Probus PA36501-EN-12101111.4 Industrial property rightsVEGA product lines are global protected by industrial property

Seite 82 - 11.5 Trademark

83INDEXVEGAPULS 61 • Probus PA36501-EN-121011INDEXAAccessories – External indicating and adjustment unit 12 – External radio unit 13 – Indicating

Seite 83

84INDEXVEGAPULS 61 • Probus PA36501-EN-121011Software addressing 33Status bytes PA output value 72Status messages 54Storage 12Surge pipe 22TTel

Seite 84

85NotesVEGAPULS 61 • Probus PA36501-EN-121011

Seite 85

86NotesVEGAPULS 61 • Probus PA36501-EN-121011

Seite 86

87NotesVEGAPULS 61 • Probus PA36501-EN-121011

Seite 87

Printing date:VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermany36501-EN-121011All statements concerning scope of delivery, application, practi

Seite 88 - Printing date:

92 For your safetyVEGAPULS 61 • Probus PA36501-EN-1210112.9 Environmental instructionsProtection of the environment is one of our most important du

Kommentare zu diesen Handbüchern

Keine Kommentare