4 Mounting
VEGAPULS 61 • Probus PA
36501-EN-121011
The measurement through a ball valve with complete run is pos-
sible
Constructional requirements on the bypass pipe:
Material metal, smoother inner tube
In case of an extremely rough tube inner surface, use an inserted
tube (tube in tube) or a radar sensor with tube antenna
Flanges are welded to the tube according to the orientation of the
polarisation level
Gap size with junctions ≤ 0.1 mm, for example, when using a ball
valve or intermediate anges with single pipe sections
The antenna diameter of the sensor should correspond to the
inner diameter of the tube
Diameter should be constant over the complete length
The short examples give you introductory information on the ow
measurement. Detailed planning information is available from ume
manufacturers and in special literature.
h
max
d
min
≥ 2 mm x h
max
90°
4
3 ... 4 h
max
≥ 50 mm
90°
2 3
1
Fig.22:Flowmeasurementwithrectangularume:d
min.
= min. distance of the
sensor (see chapter "Technical data"); h
max.
=max.llingoftherectangular
ume
1 Overoworice(sideview)
2 Headwater
3 Tail water
4 Overfallorice(viewfrombottomwater)
In general, the following points must be observed:
Install the sensor on the headwater side
Installation in the centre of the ume and vertical to the liquid
surface
Distance to the overfall orice
Distance of orice opening above ground
Min. distance of the orice opening to bottom water
Min. distance of the sensor to max. storage level
Flow measurement with
rectangularume