Operating InstructionsRadar sensor for continuous level measurement of liquidsVEGAPULS 62Modbus and Levelmaster protocolDocument ID: 41362
103 Product descriptionVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-1210113 Product description3.1 CongurationThe type label contains the
113 Product descriptionVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-12101121Fig. 5: Position of Modbus and sensor electronics1 Modbus electr
123 Product descriptionVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-121011 – Storage tanks and process vessels, measurement of products such
133 Product descriptionVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-1210113.4 Accessories and replacement partsThe indicating and adjustment
144 MountingVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-1210114 Mounting4.1 General instructionsWith instruments with threaded process tti
154 MountingVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-1210113 4 1 2 Fig. 6: Dismounting of the horn antenna1 Marking of the polarisation
164 MountingVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-121011cient air ow (the air is led through the holes to the feed system. A rinsing
174 MountingVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-121011is expected. In this case, we recommend repeating a false echo stor-age later
184 MountingVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-121011Fig.11:MountingoftheradarsensorwithinowingmediumThe socket piece sho
194 MountingVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-121011sensor increases. Additional false reections may be generated which can inue
2Quick startVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-121011Quick startThe quick start enables a quick setup with many applications. You c
204 MountingVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-121011Socket diameter d Socket length h Recommended anten-na diameter40 mm 100 mm 40
214 MountingVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-121011Small, inclined sheet metal baes above the installations scatter the radar si
224 MountingVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-1210110%100%123123458679Fig.20:Congurationsurgepipe1 Radar sensor2 Marking of
234 MountingVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-121011Constructional requirements on the surge pipe:• Material metal, smoother inner
244 MountingVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-121011Instructions for orientation:• Note marking of the polarisation plane on the s
254 MountingVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-121011max. 50 mm (1.97")123Fig. 22: Mounting of the instrument with ins
264 MountingVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-1210113 ... 4 hmax≥ 50 mm90°231hmaxdmin≥ 2 mm x hmax90°42 3Fig.24:Flowmeasurement
274 MountingVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-12101123 ... 4 x hmax90°hmaxdB1Fig.25:FlowmeasurementwithKhafagi-Venturiume:
285 Connecting to power supply and bus systemVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-1210115 Connecting to power supply and bus system5
295 Connecting to power supply and bus systemVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-121011The connection to the indicating and adjustme
3Quick startVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-1210114. Carry out the adjustment in the menu items "Min. adjustment" and
305 Connecting to power supply and bus systemVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-12101110. Place probably existing indicating and a
315 Connecting to power supply and bus systemVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-121011++power supplyMODBUSD0D1IS GNDUSB1213452off
326 Set up the sensor with the indicating and adjustment moduleVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-1210116 Set up the sensor with t
336 Set up the sensor with the indicating and adjustment moduleVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-1210116.3 Adjustment system12Fig
346 Set up the sensor with the indicating and adjustment moduleVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-121011Setup: Settings, for exampl
356 Set up the sensor with the indicating and adjustment moduleVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-121011The following options are a
366 Set up the sensor with the indicating and adjustment moduleVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-121011• Product speed: – Fast to
376 Set up the sensor with the indicating and adjustment moduleVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-121011• Process/measurement condi
386 Set up the sensor with the indicating and adjustment moduleVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-121011If you want to measure the
396 Set up the sensor with the indicating and adjustment moduleVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-121011• Adjustment for all applic
4ContentsVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-121011Contents1 About this document1.1 Function ...
406 Set up the sensor with the indicating and adjustment moduleVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-121011100%0%0,5 m(19.68")5 m
416 Set up the sensor with the indicating and adjustment moduleVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-1210114. Enter the suitable dist
426 Set up the sensor with the indicating and adjustment moduleVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-121011The "Echocurve"
436 Set up the sensor with the indicating and adjustment moduleVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-121011• High sockets• Vessel inst
446 Set up the sensor with the indicating and adjustment moduleVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-121011The menu item "Delete&
456 Set up the sensor with the indicating and adjustment moduleVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-121011• Setup: Resetting of the p
466 Set up the sensor with the indicating and adjustment moduleVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-121011If the instrument is equipp
477 Setting up sensor and Modbus interface with PACTwareVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-1210117 Setting up sensor and Modbus in
487 Setting up sensor and Modbus interface with PACTwareVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-121011The connection of the PC to the RS
497 Setting up sensor and Modbus interface with PACTwareVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-121011Fig.36:ExampleofaDTMviewAll
5ContentsVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-1210118.5 Exchanging the electronics module ... 578.6
508 Diagnosis, Asset Management and serviceVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-1210118 Diagnosis, Asset Management and service8.1 M
518 Diagnosis, Asset Management and serviceVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-121011Further echo curves: Up to 10 echo curves can b
528 Diagnosis, Asset Management and serviceVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-121011The following table shows the codes and text me
538 Diagnosis, Asset Management and serviceVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-121011CodeText mes-sageCause Rectication PA DevS-pec
548 Diagnosis, Asset Management and serviceVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-121011The following table shows the error codes and t
558 Diagnosis, Asset Management and serviceVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-121011The below tables show typical examples of appli
568 Diagnosis, Asset Management and serviceVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-1210118.4 MeasurementerrorduringllingFault descr
578 Diagnosis, Asset Management and serviceVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-1210118.4 Measurement error during emptyingFault des
588 Diagnosis, Asset Management and serviceVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-121011In both cases, the serial number of the sensor
599 DismountingVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-1210119 Dismounting9.1 Dismounting stepsWarning:Before dismounting, be aware of
61 About this documentVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-1210111 About this document1.1 FunctionThis operating instructions manual
6010 SupplementVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-12101110 Supplement10.1 Technical dataGeneral data316L corresponds to 1.4404 or
6110 SupplementVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-121011Input variableMeasured variable The measured quantity is the distance betwe
6210 SupplementVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-121011 Ʋ Protocols Modbus RTU, Modbus ASCII, LevelmasterMax. transmission rate 9.
6310 SupplementVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-121011Gas phase Temperature Pressure1 bar (14.5 psig)10 bar (145 psig)50 bar (725
6410 SupplementVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-121011Process conditionsFor the process conditions, please also note the specica
6510 SupplementVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-121011 Ʋ 0.5 bar (7.25 psig) 3.5 m3/h Ʋ 1 bar (14.5 psig) 4.5 m3/h Ʋ 1.5 bar (21.
6610 SupplementVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-121011 Ʋ Inspection window Polyester foilIntegrated clockDate format Day.Month.Ye
6710 SupplementVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-121011twisted two-wire cable can be up to 1200 m. The bus must be terminated on b
6810 SupplementVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-12101110.2 GeneralcongurationofthehostThe data exchange with status and var
6910 SupplementVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-121011Register Name Register Number Type NoteSV 110 Secondary Variable in Byte Or
72 For your safetyVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-1210112 For your safety2.1 Authorised personnelAll operations described in t
7010 SupplementVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-121011Register Name Register Number Type NotePV 2202 DWord Primary Variable in By
7110 SupplementVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-12101110.4 FC4 Read Input RegisterWith this command, any number (1-127) of input
7210 SupplementVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-121011Implemented function codes:Sub Function Code Name0x00 Return Data Request0x
7310 SupplementVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-121011Parameter Length Code/DataMEI Type 1 Byte 0x0ERead Device ID Code 1 Byte 0x
7410 SupplementVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-121011• "*" can be used as a joker for any position in the address. The
7510 SupplementVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-12101110.5 Set number of FloatsRequest:Parameter Length Code/DataSet number of F
7610 SupplementVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-121011Response:Parameter Length Code/DataSet Receive to Transmit Delay 5 characte
7710 SupplementVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-12101110.6 CongurationoftypicalModbushosts10.6 Fisher ROC 809Wiring plan++
7810 SupplementVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-12101110.6 ABB Total FlowWiring plan++power supplyMODBUSD0D1IS GNDUSB1 213452o
7910 SupplementVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-12101110.6 Thermo Electron AutopilotWiring plan++power supplyMODBUSD0D1IS GNDU
82 For your safetyVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-1210112.5 CE conformityThe device fullls the legal requirements of the appli
8010 SupplementVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-12101110.6 Bristol ControlWave MicroWiring plan++power supplyMODBUSD0D1IS GNDU
8110 SupplementVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-12101110.6 ScadaPackWiring plan++power supplyMODBUSD0D1IS GNDUSB132134552134967
8210 SupplementVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-121011Housing1~ 87 mm (3.43")M16x1,5ø 84 mm(3.31")120 mm (4.72")M2
8310 SupplementVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-121011VEGAPULS62,hornantennainangeversionxy2160 mm(2.36")mminch8.50&q
8410 SupplementVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-121011VEGAPULS62,hornantennainangeversion450°Cyxinch8.50"11.30"
8510 SupplementVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-121011VEGAPULS 62, horn antenna and swivelling holdermm inch 20 mm(0.79")20
8610 SupplementVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-121011VEGAPULS 62, parabolic antenna and swivelling holder130 mm (5.12")ø 24
8710 SupplementVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-12101110.8 Industrial property rightsVEGA product lines are global protected by
Printing date:VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermany41362-EN-121011All statements concerning scope of delivery, application, practi
92 For your safetyVEGAPULS 62 • Modbus and Levelmaster protocol41362-EN-121011tection. The environment management system is certied according to DIN