9 Diagnostics and service
FIBERTRAC 31 • 4 … 20 mA/HART - four-wire
43386-EN-131119
Code
Text mes-
sage
Cause Rectication
S017
Accuracy
outside the
specication
Accuracy outside the
specication
Correct adjustment data
S025
Bad lineariza-
tion table
Bad linearization table Carry out linearization
S038
Slave outside
thespecica-
tion
Slaveoutsidethespecica-
tion
Check Slave
S125
Ambient tem-
perature too
high/too low
Ambient temperature too
high/too low
Protect instrument with
isolating material against
extreme temperatures
The instrument has no status messages to the section "Maintenance".
9.3 Rectify faults
The operator of the system is responsible for taking suitable meas-
ures to rectify faults.
Therstmeasuresare:
Evaluation of fault messages, for example via the display and
adjustment module
Checking the output signal
Treatment of measurement errors
Further comprehensive diagnostics options are available with a PC
with PACTware and the suitable DTM. In many cases, the reasons can
bedeterminedinthiswayandfaultsrectied.
Connect a multimeter in the suitable measuring range according to
the wiring plan. The following table describes possible errors in the
current signal and helps to remove them:
Error Cause Rectication
4 … 20 mA signal
not stable
Leveluctuations Set damping according to the instru-
ment via the display and adjustment
module or PACTware/DTM
Maintenance
Reaction when malfunc-
tions occur
Procedure for fault recti-
cation
Check 4 … 20 mA signal
(level measurement)