10 Supplement
VEGABAR 52 • Probus PA
36719-EN-130321
Referenceconditionsandactuatingvariables(accordingtoDINEN60770-1)
Reference conditions according to DIN EN 61298-1
Ʋ Temperature +15 … +25 °C (+59 … +77 °F)
Ʋ Relative humidity 45 … 75 %
Ʋ Air pressure 860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psig)
Determination of characteristics Limit point adjustment according to IEC 61298-2
Characterstic curve Linear
Reference installation position upright, diaphragm points downward
Inuence of the installation position
< 0.2 mbar/20 Pa (0.003 psig)
Deviation determined according to the limit point method according to IEC 60770
5)
Applies to the digital signal output (HART, Probus PA, Foundation Fieldbus) as well as to ana-
logue current output 4 … 20 mA and refers to the set span. Turn down (TD) is the ratio nominal
measuring range/set span.
Deviation with absolutely ush process ttings EV, FT
Ʋ Turn down 1 : 1 up to 5 : 1 < 0.05 %
Ʋ Turn down > 5 : 1 < 0.01 % x TD
Deviation with version 0.075 %
Ʋ Turn down 1 : 1 up to 5 : 1 < 0.075 %
Ʋ Turn down > 5 : 1 < 0.015 % x TD
Deviation with version 0.1 %
Ʋ Turn down 1 : 1 up to 5 : 1 < 0.1 %
Ʋ Turn down > 5 : 1 < 0.02 % x TD
Deviation with version 0.2 %
Ʋ Turn down 1 : 1 up to 5 : 1 < 0.2 %
Ʋ Turn down > 5 : 1 < 0.04 % x TD
Deviation with absolute pressure measuring range 0.1 bar
Ʋ Turn down 1 : 1 up to 5 : 1 < 0.25 %
Ʋ Turn down > 5 : 1 < 0.05 % x TD
Inuenceoftheproductorambienttemperature
Thermal change zero signal and output span
Applies to the digital signal output (HART, Probus PA, Foundation Fieldbus) as well as to ana-
logue
current output 4 … 20 mA and refers to the set span. Turn down (TD) is the ratio nominal
measuring range/set span.
Thermal change zero signal and output span, reference temperature 20 °C (68 °F):
Ʋ In the compensated temperature
range 0 … +100 °C (+32 … +212 °F)
< (0.05 % + 0.1 % x TD)
Ʋ Outside the compensated tempera-
ture range
< (0.05 % + 0.15 % x TD)
Thermal change zero signal and output span with absolute pressure measuring range 0.1 bar,
reference temperature 20 °C (68 °F):
5)
Incl. non-linearity, hysteresis and non-repeatability.