1000
750
500
250
12 18
1614 20 22 24 26 28 30 32 34 36
Ω
V
4
1
2
3
Fig. 30: Voltage diagram
1 HART load
2 Voltage limit EEx-ia
instrument
3 Voltage limit non-Ex/Exd instrument
4 Operating voltage
Electrical protective measures
Protection class
- Housing, standard IP 66/IP 67
15)
- Aluminium and stainless housing (op-
tionally available)
IP 68 (1 bar)
16)
- Transmitter in IP 68 version IP 68
- External housing IP 65
Overvoltage category III
Protection class II
Functional safety (SIL)
The functional safety is already activated Ex factory for instruments with SIL qu alification. For
instruments Ex factory without SIL qualification, the functional safety must be activated by the user
for applications according to SIL via the indicating and adjustment module or via PACTware.
Functional safety according to IEC 61508-4
- Single channel architecture (1oo1D) up to SIL2
- double channel diversitary redundant
architecture (1oo2D)
up to SIL3
15)
Instruments with gauge pressure measuring ranges cannot detect the am-
bient pressure when submerged, e.g. in water. This can lead to falsification
of the measured value.
16)
Only with instruments with absolute pressure ranges.
62 VEGABAR 64 • 4 … 20 mA/HAR
T