10 Supplement
VEGABAR 66 • Foundation Fieldbus
36740-EN-130321
XandYvaluesfortheuserdenedlinearizationcurve
curve_points_11_20
XandYvaluesfortheuserdenedlinearizationcurve
curve_points_21_30
XandYvaluesfortheuserdenedlinearizationcurve
curve_points_31_33
XandYvaluesfortheuserdenedlinearizationcurve
curve status
Result of table plausibility check
"0:""Uninitialized""1:""Good""2:""Notmonotonousincreasing""3:""Notmonotonous
decreasing""4:""Notenoughvaluestransmitted""5:""Toomanyvaluestransmitted""6:""Gra-
dientofedgetoohigh""7:""Valuesnotexcepted""8:""Tablecurrentlyloaded""9:""Sortingand
checkingtable"""
SUB_DEVICE_NUMBER
SENSOR_ELEMENT_TYPE
0:"non-specic"
display_source_selector
Selects the type of value that is displayed on the indication-/adjustement-module
"0:""Physicalvalue""1:""Percentvalue""2:""Linpercentvalue""6:""Out(AI1)""7:""Level""8:
""Out(AI2)""9:""Out(AI3)"""
max_peak_sensor_value
Holdsthemaximumsensorvalue.Writeaccessresetstocurrentvalue.Unitderivesfrom'Sen-
sor_range.unit'
Write access resets to current value
min_peak_sensor_value
Holdstheminimumsensorvalue.Writeaccessresetstocurrentvalue.Unitderivesfrom'Sen-
sor_range.unit'
Write access resets to current value
CAL_POINT_HI
Highest calibrated value. For calibration of the high limit point you give the high measurement
value(pressure)tothesensorandtransferthispointasHIGHtothetransmitter.Unitderives
from 'Sensor_range.unit'
CAL_POINT_LO
Lowest calibrated value. For calibration of the low limit point you give the low measurement
value(pressure)tothesensorandtransferthispointasLOWtothetransmitter.Unitderives
from 'Sensor_range.unit'
CAL_MIN_SPAN
Minimum calibration span value allowed. Necessary to ensure that when calibration is done,
thetwocalibratedpoints(highandlow)arenottooclosetogether.Unitderivesfrom'Sen-
sor_range.unit'
SCALE_IN
Min/max-adjustment:Upperandlowercalibratedpointsofthesensor.Unitderivesfrom'Sen-
sor_range.unit'
trimmed_value
Sensorvalueafterthetrimprocessing.Unitderivesfrom'Sensor_range.unit'
sensor_sn
Sensor serial number
temperature
Processtemperature.SelectedasinputtoAIFBbysetting'Channel'=4.Unitderivesfrom
'Temperature.unit'
temperature_unit
Unitcodeof'Temperature','Max/Min_peak_temperature_value'
°C, °F, K, °R