10 Supplement
VEGABAR 66 • Foundation Fieldbus
36740-EN-130321
– XandYvaluesfortheuserdenedlinearizationcurve
•
curve_points_11_20
– XandYvaluesfortheuserdenedlinearizationcurve
•
curve_points_21_30
– XandYvaluesfortheuserdenedlinearizationcurve
•
curve_points_31_33
– XandYvaluesfortheuserdenedlinearizationcurve
•
curve status
– Result of table plausibility check
– "0:""Uninitialized""1:""Good""2:""Notmonotonousincreasing""3:""Notmonotonous
decreasing""4:""Notenoughvaluestransmitted""5:""Toomanyvaluestransmitted""6:""Gra-
dientofedgetoohigh""7:""Valuesnotexcepted""8:""Tablecurrentlyloaded""9:""Sortingand
checkingtable"""
•
SUB_DEVICE_NUMBER
•
SENSOR_ELEMENT_TYPE
– 0:"non-specic"
•
display_source_selector
– Selects the type of value that is displayed on the indication-/adjustement-module
– "0:""Physicalvalue""1:""Percentvalue""2:""Linpercentvalue""6:""Out(AI1)""7:""Level""8:
""Out(AI2)""9:""Out(AI3)"""
•
max_peak_sensor_value
– Holdsthemaximumsensorvalue.Writeaccessresetstocurrentvalue.Unitderivesfrom'Sen-
sor_range.unit'
– Write access resets to current value
•
min_peak_sensor_value
– Holdstheminimumsensorvalue.Writeaccessresetstocurrentvalue.Unitderivesfrom'Sen-
sor_range.unit'
– Write access resets to current value
•
CAL_POINT_HI
– Highest calibrated value. For calibration of the high limit point you give the high measurement
value(pressure)tothesensorandtransferthispointasHIGHtothetransmitter.Unitderives
from 'Sensor_range.unit'
•
CAL_POINT_LO
– Lowest calibrated value. For calibration of the low limit point you give the low measurement
value(pressure)tothesensorandtransferthispointasLOWtothetransmitter.Unitderives
from 'Sensor_range.unit'
•
CAL_MIN_SPAN
– Minimum calibration span value allowed. Necessary to ensure that when calibration is done,
thetwocalibratedpoints(highandlow)arenottooclosetogether.Unitderivesfrom'Sen-
sor_range.unit'
•
SCALE_IN
– Min/max-adjustment:Upperandlowercalibratedpointsofthesensor.Unitderivesfrom'Sen-
sor_range.unit'
•
trimmed_value
– Sensorvalueafterthetrimprocessing.Unitderivesfrom'Sensor_range.unit'
•
sensor_sn
– Sensor serial number
•
temperature
– Processtemperature.SelectedasinputtoAIFBbysetting'Channel'=4.Unitderivesfrom
'Temperature.unit'
•
temperature_unit
– Unitcodeof'Temperature','Max/Min_peak_temperature_value'
– °C, °F, K, °R