Vega FIBERTRAC 31 4 … 20 mA_HART - four-wire With SIL q Bedienungsanleitung Seite 76

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 88
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 75
76
11 Supplement
FIBERTRAC 31 • 4 … 20 mA/HART - four-wire
43386-EN-131119
Ʋ Max. 3 A AC, 1 A DC
Breaking capacity
Ʋ Min. 50 mW
Ʋ Max. 750VAAC,40WDC
If inductive loads or stronger currents are switched
through, the gold plating on the relay contact surface will
be permanently damaged. The contact is then no longer
suitable for switching low-level signal circuits.
Contact material (relay contacts) AgNi or AgSnO and Au plated
Accuracy (according to DIN EN 60770-1)
Process reference conditions according to DIN EN 61298-1
Ʋ Temperature +18 … +30 °C (+64 … +86 °F)
Ʋ Relative humidity 45 … 75 %
Ʋ Air pressure 860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psig)
Repeatability ≤0.5%
Deviation with bulk solids The values depend to a great extent on the application.
Bindingspecicationsarethusnotpossible.
DeviationunderEMCinuence ≤1%
Variablesinuencingmeasurementaccuracy
Specicationsapplyalsotothecurrentoutput
Temperature drift - Current output ±0.03 %/10 K relating to the 16 mA span max. ±0.3 %
Deviation on the current output through
analogue/digital conversion
<±15 µA
Deviation on the current output due to
strong, high frequency electromagnetic
interference acc. to EN 61326
<±150 µA
Characteristics and performance data
Step response time
5)
≤5s(withdamping1s)
Ambient conditions
Ambient, storage and transport tempera-
ture
-40 … +60 °C (-40 … +140 °F)
Process conditions
Fortheprocessconditions,pleasealsonotethespecicationsonthetypelabel.Thelowervalue
always applies.
Process pressure Unpressurized
5)
Time span after a sudden measuring distance change by max. 0.5 m in liquid applications, max 2 m with bulk
solidsapplications,untiltheoutputsignalhastakenforthersttime90%ofthenalvalue(IEC61298-2).