24
4Mounting
VEGADIF 65 • 4 … 20 mA
36236-EN-130417
1. MountVEGADIF65directlytothevessel
2. Minussideisopentotheatmosphericpressure
+
min.
p
atm
p
atm
1
2
+ –
Fig. 21: Measurement setup, level measurement in the open vessel
1 VEGADIF 65
2 Minus side is open to the atmospheric pressure
1. MountVEGADIF65belowthelowermeasurementconnectionso
thattheeectivepressurelinesarealwayslledwithliquid
2. Connectminussidealwaysabovethemax.level
3. Formeasurementsinproductswithsolidcontentsuchase.g.
dirtyliquids,theinstallationofseparatorsanddrainvalvesis
recommended to enable collection and removal of debris and
sediment.
+
–
min.
max.
1
3
4
3
4
5
1
2
Fig. 22: Measurement setup, level measurement in closed vessel
1 Blocking valves
2 VEGADIF 65
3 Separator
4 Drain valves
5 3-fold valve block
In open vessels with
single chemical seal
In closed vessels with ef-
fective pressure lines