Vega VEGADIF 65 4 … 20 mA Bedienungsanleitung Seite 27

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 88
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 26
27
4Mounting
VEGADIF 65 • 4 … 20 mA
36236-EN-130417
+
min.
max.
1
2
3
4
5
+
Fig. 26: Measurement setup in closed vessel with superimposed steam
1 Condensate vessel
2 Blocking valve
3 Separator
4 Drain valve
5 VEGADIF 65
4.6 Measurement setup density and interface
Inavesselwithvaryinglevelandhomogeneousdensitydistribution,
densitymeasurementwithadierentialpressuretransmittercanbe
realized.Theconnectiontothevesselismadeviaachemicalsealon
twomeasuringpoints.Toreachahighaccuracy,thedistancebetween
these points must be as big as possible. The density measurement is
onlyensuredwithalevelabovetheuppermeasuringpoint.Ifthelevel
dropsbelowtheuppermeasuringpoint,thedensitymeasurementis
interrupted.
Thisdensitymeasurementfunctionswithopenbutalsowithclosed
vessels.Makesurethatsmalldensitychangescauseonlysmall
changestothemeasureddierentialpressure.Selectasuitable
measuring range.
The density measurement is carried out in the mode level measure-
ment.
1. MountVEGADIF65belowthelowerchemicalseal
2. The ambient temperature should be the same for both capillaries
Example for a density measurement:
Distancebetweenthetwomeasurementpoints:0.3m
Min.density:1000kg/m³
Max.density:1200kg/m³
Measureddierentialpressure:Δp=ρ•g•h
Themin.adjustmentiscarriedoutforthedierentialpressuremeas-
ured at density 1.0:
Δp=ρ•g•h
=1000kg/m³•9.81m/s
2
• 0,3 m
=2943Pa=29.43mbar
Density measurement
Seitenansicht 26
1 2 ... 22 23 24 25 26 27 28 29 30 31 32 ... 87 88

Kommentare zu diesen Handbüchern

Keine Kommentare