4Mounting
VEGADIF 65 • 4 … 20 mA
36236-EN-130417
Themax.adjustmentiscarriedoutforthedierentialpressuremeas-
ured at density 1.2:
Δp=ρ•g•h
=1200kg/m³•9.81m/s
2
• 0.3 m
=3531Pa=35.31mbar
=
∆p
h
g
+
–
0,3 m
Fig. 27: Measurement setup with density measurement
Inavesselwithvaryinglevel,aninterfacemeasurementwithadif-
ferentialpressuretransmittercanberealized.Theconnectiononthe
vesseliscarriedoutviaachemicalsealontwomeasuringpoints.
Aninterfacemeasurementisonlypossibleifthedensitiesofthetwo
productsremainthesameandtheinterfaceisalwaysbetweenthe
twomeasuringpoints.Thetotallevelmustalwaysbeabovetheupper
measuring point.
Thisdensitymeasurementfunctionswithopenbutalsowithclosed
vessel.
Example for an interface measurement:
Distancebetweenthetwomeasurementpoints:0.3m
Min.density:800kg/m³
Max.density:1000kg/m³
Themin.adjustmentiscarriedoutforthedierentialpressureoccur-
ingwithdensity0.8:
Δp=ρ•g•h
=800kg/m³•9.81m/s•0.3m
=2354Pa=23.54mbar
Themax.adjustmentiscarriedoutforthedierentialpressureoccur-
ingwithdensity1.0:
Δp=ρ•g•h
=1000kg/m³•9.81m/s•0.3m
=2943Pa=29.43mbar
3. MountVEGADIF65belowthelowerchemicalseal
4. The ambient temperature should be the same for both capillaries
Interface measurement