34 VEGACOM 557 Profibus FMS
Setup
Saving of measured values blocks in measured value data components
For saving the measured values, the data components DB220 to DB235 are set as a standard
feature. The Start data component can be set in DB240 in DW0 (standard: 220). The next 16
data components must be reserved for the measured values.
DB (measured value block) = Start data component + measured value block -1
Start data component = 220 (standard setting); measured value block = 1 … 16
Initialisation of the measured value data components (DB 220-235)
Each measured value block is saved in a data component. For the 16 measured value blocks,
16 data components with 16 measured values each are required. As a standard feature, data
components DB220 to DB235 are set. The Start data component can be set in DB240 in DW 0
(standard: 220). The next 16 data components must be reserved for the measured values.
The initialisation values must be entered in the data components.
A measured value consists of 4 octetts and one index and status information (6 octetts = 3
data words)
Index Status HI/LO (1 octett)
Measured value (4 octetts)
0: KH = FFFE; Index=FF Status=FE
1: KH = 0000; Meas. value 1
2: KH = 0000;
3: KH = FFFE;
4: KH = 0000; Meas. value 2
5: KH = 0000;
6: KH = FFFE;
7: KH = 0000; Meas. value 3
8: KH = 0000;
9: KH = FFFE;
10: KH = 0000; Meas. value 4
11: KH = 0000;
12: KH = FFFE;
13: KH = 0000; Meas. value 5
14: KH = 0000;
... ... ...
45: KH = FFFE;
46: KH = 0000; Meas. value 16
47: KH = 0000;