8 Maintenance and fault rectification
8.1 Maintena
nce
When used as directed in normal operation, VEGAPULS 61 is
completely maintenance free.
8.2 Rectify malfunctions
The operator of the system is responsible for taking suitable measures
to remove interferences.
VEGAPULS 61 offers maximum reliability. Nevertheless, faults can
occur during operation. These may be caused by the following, e.g.:
l Sensor
l Process
l Voltage supply
l Signal processing
The first measures to be taken are to check the output signals as well
as to evaluate the error messages via the indicating and adjustment
module. The procedure is described below. Further comprehensive
diagnostics can be carried out on a PC with the software PACTware
and the suitable DTM. In many cases, the causes can be determined
this way and faults rectified.
However, should these measures not be successful, call the VEGA
service hotline in urgent cases under the phone no. +49 1805 858550.
The hotline is available to you 7 days a week round-the-clock. Since
we offer this service world-wide, the support is only available in the
English language. The service is free of charge, only the standard
telephone costs will be charged.
Connect a handmultimeter in the suitable measuring range according
to the wiring plan. The following table describes possible errors in the
current signal and helps to remove them:
Error Cause Removal
4 … 20 mA signal
not stable
Level fluctuations Set damping via the indicating and
adjustment module
4 … 20 mA signal
missing
Electrical con-
nection faulty
Check connection according to chap-
ter "Connection steps" and if ne-
cessary, correct according to chapter
"Wiring plan"
Reaction when malfunc-
tions occur
Causes of malfunction
Fault rectification
24 hour service hotline
Checking the 4 … 20 mA
signal
50 VEGAPULS 61 • 4 … 20 mA/HAR
T two-wire
8 Maintenance and fault rectificati
on
28434-EN-100426