Error Cause Removal
Voltage supply
missing
Check cables
for breaks; repair if
necessary
Operating voltage
too low or load
resistance too
high
Check, adapt if necessary
Current signal
greaterthan 22 mA
or less than
3.6 mA
Oscillator in the
sensor defective
Exchange the instrument or send it in
for repair
In Ex applications, the regu
lations for the wiring of intrinsically safe
circuits must be observed.
? E013
l no measured value available
à Sensor in boot phase
à Sensor does not nd an echo, e.g. due to faulty installation or
wrong parameter adjustment
? E017
l Adjustment span too small
à Carry out a fresh adjustment and increase the distance
between min. and max. adjustment
? E036
l no operable sensor software
à Carry out a software update or send instrument for repair
? E041, E042, E043
l Hardware error, electronics defective
à Exchange the instrument or send it in for repair
Depending on the failure reason and measures taken, the steps
described in chapter "Set up" must be carried out again, if necessary.
8.3 Exchanging the electronics module
If the electronics module is defective, it can be replaced by the user.
In Ex applications only one instrument and one electronics module with
respective Ex approval may be used.
Fault messages via the
indicating/adjustment
module
Reaction after fault rec-
tication
VEGAPULS 61 4 20 mA/HART two-wire 51
8 Maintenance and fault recticati
on