In vessels with conical bottom it can be advantageous to mount the
sensor in
the center of the vessel, as measurement is then possible
down to the lowest point of the vessel bottom.
Fig. 8: Vessel with conical
bottom
Do not mount the instruments in or above the lling stream. Make sure
that you detect the product surface, not the inowing product.
Fig. 9: Inowing liquid
The
socket piece should be dimensioned in such a way that the
antenna end protrudes at least 10 mm (0.4 in) out of the socket.
Inowing medium
Socket
16 VEGAPULS 61 4 20 mA/HAR
T two-wire